Instructions
21 ADAM-6000 User Manual
Chapter 4 Introduction to Analog ADAM-6000 I
/
O Modules
Analog Input
Channels: 8 (differential)
Input impedance: >10 M (voltage), 120 (current)
Input type: mV, V, mA
Input range: ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, 0~150 mV, 0~500 mV, 0~1 V,
0~5 V, 0~10 V, 0~20 mA, 4~20 mA, ±20 mA
Accuracy:
– ±0.1% of FSR (voltage) @ 25°C
– ±0.2% of FSR (current) @ 25°C
Span drift: ±25 ppm/°C
Zero drift: ±6 mV/°C
Resolution: 16-bit
Sample rate (total):
– 10 Hz
– 100 Hz (CE version only)
CMR @ 50/60 Hz: 90 dB
NMR @ 50/60 Hz: 67 dB
Calibration: Auto calibration
Burnout detection (4~20 mA only)
Common-mode voltage: 350 V
DC
Digital Output
Channels: 2
Sink type: Open collector to 30 V, 100 mA (max. load)
Power dissipation: 300 mW for each module
Output-delay on: 100 µs
Output-delay off: 150 µs
Overvoltage protection (max.): 42 V
DC
Overcurrent protection (max.): 2 A
Leakage current: 200 µA (max.) for D version
General
Isolation protection: 2000 V
DC
Power input: 10~30 V
DC
Power consumption: 2.7 W @ 24 V
DC
Power reversal protection
Operating humidity: 20~95% RH (non-condensing)
Storage humidity: 0~95% RH (non-condensing)
Operating temp (exclusive of RTC function): -20~70°C (-40~70°C for D version)
Storage temp (exclusive of RTC function): -30~80°C (-40~85°C for D version)
Watchdog timer (system): 1.6 s
RTC (D version only): ISO8601 format
Note! The operation/storage temperature for the RTC function is -30~70°C.