User Manual

43 Chapter 4
Assigning Addresses in ADAM-6050 Modules
Basing on Modbus/TCP standard, the addresses of the I/O channels in
ADAM-6000 modules you place in the system are defined by a simple
rule. Please refer to Appendix B.2.5 to map the I/O address. All digital
input channels in ADAM-6050 are allowed to use as 32-bit counters
(Each counter is consisted of two addresses, Low word and High word).
Users could configure the specific DI channels to be counters via Win-
dows Utility. (Refer to Section 5.3)
4.2.2 ADAM-6051
14-ch Isolated Digital Input/Output with 2-ch Counter Module
The ADAM-6051 is a high-density I/O module built-in a 10/100 based-T
interface for seamless Ethernet connectivity. It provides 12 digital input,
2 digital output, and 2 counter channels with 2000 V
DC
isolation protec-
tion. All of the digital input channels support input latch function for
important signal handling. Meanwhile, these DI channels allow to be
used as 3 kHz counter and frequency input channels. Opposite to the
intelligent DI functions, the digital output channels also support pulse
output function.
ADAM-6051 Specifications
• Communication: 10/100 Base-T Ethernet
• Supports Protocol: Modbus/TCP, TCP/IP, UDP, HTTP, ICMP, DHCP
and ARP
• Supports Peer-to-Peer and GCL (Refer to Section 5.3.5 and Chapter 7)
Digital Input
• Channels: 12
• Dry Contact:
Logic level 0: Close to GND
Logic level 1: Open
• Wet Contact:
Logic level 0: 0 ~ 3 V
DC
Logic level 1: 10 ~ 30 V
DC
• Supports 3 kHz counter input (32-bit + 1-bit overflow)
• Supports 3 kHz frequency input
• Supports inverted DI status