User Manual
ADAM-6000 Series User Manual 32
ADAM-6018 Specifications
• Communication: 10/100 Base-T Ethernet
• Supports Protocol: Modbus/TCP, TCP/IP, UDP, HTTP, ICMP, DHCP
and ARP
• Supports Peer-to-Peer and GCL (Refer to Section 5.3.5 and Chapter 7)
Analog Input
• Channels: 8 (differential)
• Input Impedance: > 10 M
• lnput Type: Thermocouple
• Thermocouple Type Range:
J Type: 0 ~ 760°C
K Type: 0 ~ 1370°C
T Type: -100 ~ 400°C
E Type: 0 ~ 1000°C
R Type: 500 ~ 1750°C
S Type: 500 ~ 1750°C
B Type: 500 ~ 1800°C
• Accuracy: ±0.1% or Better
• Span Drift: ±25 ppm/°C
• Zero Drift: ±6
V/°C
• Resolution: 16-bit
• Sampling Rate: 10 sample/second
• CMR @ 50/60 Hz: 90 dB
• NMR @ 50/60 Hz: 60 dB
• Over Voltage Protection ±35 V
DC
• Built-in TVS/ESD Protection
• Wire Burn-out Detection
Digital Output
• Channels: 8
• Sink type: Open Collector to 30 V, 100 mA (maximum load)
• Power Dissipation: 300 mW for each module