User Manual

ADAM-6000 Series User Manual 28
Digital Output:
• Channels: 2
• Sink type: Open Collector to 30 V, 100 mA (maximum load)
• Power Dissipation: 300 mW for each module
• Output Delay On:100 µs
• Output Delay Off:150 µs
• Over voltage protection (Max.): 42 V
DC
• Over current protection (Max.): 2 A
• Temperature shutdown (TSD): 175° C
General:
• Isolation Protection: 2000 V
DC
• Power Input: 10 ~ 30 V
DC
(±10%
• Power Consumption: 2.7 W @ 24 V
DC
• Power Reversal Protection
• Operating Humidity: 20 ~ 95% RH (non-condensing)
• Storage Humidity: 0 ~ 95% RH (non-condensing)
• Operating Temperature: -20 ~ 70°C
• Storage Temperature: -30 ~ 80°C
• Watchdog Timer (System): 1.6s