User Manual

25 Chapter 4
Analog Input:
• Channels: 7 (differential)
• Input Impedance: > 10
• Input Connections: 2 or 3 wire
• Input Type: Pt, Balco and Ni RTD
• RTD Types and Temperature Range:
• Pt 100: -50 ~ 150°C
0 ~ 100°C
0 ~ 200°C
0 ~ 400°C
-200 ~ 200°C
IEC RTD 100 ohms (
= 0.0385)
JIS RTD 100 ohms (
= 0.0392)
• Pt 1000: -40 ~ 160°C
• Balco 500:-30 ~ 120°C
• Ni 518: -80 ~ 100°C
0 ~ 100°C
• Accuracy: ± 0.1% or better
• Span Drift: ± 25 ppm/°C
• Zero Drift: ± 6
V/°C
• Resolution: 16-bit
• Sampling Rate: 10 sample/second
• CMR @ 50/60 Hz: 90 dB
• NMR @ 50/60 Hz: 60 dB
• Wire Burn-out Detection
• Over Voltage Protection: ±35 V
DC
• Built-in TVS/ESD Protection