ADAM-6000 Series User Manual 258
1. When the specific channel cannot detect Thermocouple signal, this
bit register will be 1.
2. User can configure the High alarm value in the ADAM.NET utility.
When AI value is higher than High alarm value, this bit will be 1.
3. User can configure the Low alarm value in the ADAM.NET utility.
When AI value is lower than the Low alarm value, this bit will be 1.
B.2.4 ADAM-6024
12-Ch Universal I/O Module
Remarks:
1. AI Status: Bit Value 0: normal
Bit Value 1: over high
Bit Value 2: over low
Bit Value 0: invalid calibration
Address
0X
Ch Description Attribute Address 4X Ch Description Attribute
00001 0 DI Value Read 40001 0 AI Value Read
00002 1 DI Value Read 40002 1 AI Value Read
40003 2 AI Value Read
00017 0 DO Value R/W 40004 3 AI Value Read
00018 1 DO Value R/W 40005 4 AI Value Read
40006 5 AI Value Read
40011 0 AO Value R/W
40012 1 AO Value R/W
40021 0
AI Status
1
Read
40022 1
AI Status
1
Read
40023 2
AI Status
1
Read
40024 3
AI Status
1
Read
40025 4
AI Status
1
Read
40026 5
AI Status
1
Read