User Manual

ADAM-6000 Series User Manual 174
#aacc
Name Read AI Value from One Channel
Description Returns the input data from a specified analog input channel
in a specified module.
Syntax #aacc(cr)
# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
slave address of the ADAM-6000 module you want to
interrogate. (Always 01)
cc (range 00-05) represents the specific channel you want to
read the input data.
(cr) is the terminating character, carriage return (0Dh).
Response >(data)(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the address does not exist.
> delimiter indicating a valid command was received.
? delimiter indicating the command was invalid.
(cr) is the terminating character, carriage return (0Dh).
Example command: #0103(cr)
response: >+10.000
Analog input channel 3 of the ADAM-6024 module at
address 01h responds with an input value +10.000.