User Manual

159 Chapter 6
Note! Write ADAM-6017-AE and ADAM-6017-BE version
Range on ADAM-6017-CE is applicable. However, we sug-
gest you write new range code in our module.
Note! For ADAM-6015, ADAM-6018 table is listed in the previ-
ous page.
Example command: $01A010147(cr)
channel 1 is set to 0x0147, which means "0~5V"
response: !010B (cr) or !010147 (cr) - setting successful
?01-setting fail
Example command: $01A0109(cr)
channel 1 set to 9, which means "+/-5V"
response: !01(cr) - setting successful
?01-setting fail
?01AVG(cr) - setting fail, because the channel is set to on
of the average channel.
ADAM-6017 Analog Input Range
Range Description CE Version
Range Code
AE & BE Version
Range Code
+/-10V 0x0143 08
+/-5V 0x0142 09
+/-1V 0x0140 0A
+/-500mV 0x0104 0B
+/-150mV 0x0103 0C
0~10V 0x0148
0~5V 0x0147
0~1V 0x0145
0~500mV 0x0106
0~150mV 0x0105
0~20mA 0x0182 0D
4~20mA 0x0180 07
+/-20mA 0x0181