User's Manual
00077 11
Counter
Start(1)/Stop(0)
R/W
00078 11 Clear Counter(1) R/W
00079 11 Clear Overflow R/W
00080 11
Latch Status/ Clear
Status
R/W
00081 12
Counter
Start(1)/Stop(0)
R/W
00082 12 Clear Counter(1) R/W
00083 12 Clear Overflow R/W
00084 12
Latch Status/ Clear
Status
R/W
00085 13
Counter
Start(1)/Stop(0)
R/W
00086 13 Clear Counter(1) R/W
00087 13 Clear Overflow R/W
00088 13
Latch Status/ Clear
Status
R/W
*Note : How to retrieve the counter/frequency value on Modbus address mapping
Example :
Counter(dec) = (value of 40002) x 65536 + (value of 40001)