User Manual
ADAM-6000 Series User Manual 84
Individual Channel Configuration
You can see analog input value and configure setting for each channel.
Simply click one of the Individual Channel Configuration items for the
interested channel. (The average channel you set in the Averaging set-
ting will also be displayed here) At the upper part of the Status Display
area, you can see the current analog input value and defined range of that
channel by the Input value and Input range text box. Refer to the pic-
ture below.
Figure 5.10: Analog Input Alarm Mode Configuration
ADAM-6015, 6017 and 6018 modules all feature built-in alarm function.
At the lower part of the Status Display area, there are two tabs to config-
ure the high alarm and low alarm for the selected channel: High alarm
and Low alarm. When the analog input value is higher than the high
alarm value, or lower than the low alarm value, the alarm condition
occurs. Then the alarm status will be activated to logic high. For ADAM-
6015 module, ADAM.NET Utility can detect the alarm status and show it
by the Alarm status LED display. For ADAM-6017 and ADAM-6018
module, when the alarm condition occurs, the Alarm status LED display
will be lit. Besides, the specified digital output channel will generate
logic high value if you build the mapping relationship between alarm and
DO channel in the DO mapping area. You can set the DO channel by
Channel combo box in the DO mapping area. After choosing the inter-
ested channel, click the Apply button.