User's Manual

Assigning addresses for the ADAM-6050W Modules
ADDR 0X CH ITEM Attribute ADDR 4X CH ITEM Attribute
00001 0 DI R 40001~40002 0 *Counter R
00002 1
DI
R 40003~40004 1
*Counter
R
00003 2
DI
R 40005~40006 2
*Counter
R
00004 3
DI
R 40007~40008 3
*Counter
R
00005 4
DI
R 40009~40010 4
*Counter
R
00006 5
DI
R 40011~40012 5
*Counter
R
00007 6
DI
R 40013~40014 6
*Counter
R
00008 7
DI
R 40015~40016 7
*Counter
R
00009 8
DI
R 40017~40018 8
*Counter
R
00010 9
DI
R 40019~40020 9
*Counter
R
00011 10
DI
R 40021~40022 10
*Counter
R
00012 11
DI
R 40023~40024 11
*Counter
R
00017 0 DO R/W 40025~40026 0
Pulse Output
Low Level
R
00018 1 DO R/W 40027~40028 1
Pulse Output
Low Level
R
00019 2 DO R/W 40029~40030 0
Pulse Output
Low Level
R
00020 3 DO R/W 40031~40032 1
Pulse Output
Low Level
R
00021 4 DO R/W 40033~40034 0
Pulse Output
Low Level
R
00022 5 DO R/W 40035~40036 1
Pulse Output
Low Level
R
00033 0
Counter
Start(1)/Stop(0)
R/W 40037~40038 0
Pulse Output
High Level
R
00034 0 Clear Counter(1) R/W 40039~40040 1
Pulse Output
High Level
R
00035 0 Clear Overflow R/W 40041~40042 2
Pulse Output
High Level
00036 0
Latch Status/ Clear
Status
R/W 40043~40044 3
Pulse Output
High Level
00037 1
Counter
Start(1)/Stop(0)
R/W 40045~40046 4
Pulse Output
High Level
R
00038 1 Clear Counter(1) R/W 40047~40048 5
Pulse Output
High Level
R
00039 1 Clear Overflow R/W
00040 1
Latch Status/ Clear
Status
R/W
00041 2
Counter
Start(1)/Stop(0)
R/W