5-3-5 Alarm Setting To satisfy the needs of various applications, 
ADAM-5000/TCP Series system provides Alarm setting function for 
Analog Input and Counter Module. Users can set High/Low limit value 
to identify the alarm status and trig- ger a digital output as an event 
handling function. 
Figure 5-16: Alarm Setting for Analog Input and Counter Modules 
There are three alarm types in Analog Input Modules: 
Disable: ADAM-5000/TCP Series dose not executive alarm 
diagnosing func- tion. 
Momentary: When the Input value is over or under the High/Low limit, 
the alarm signal will be sent only once. 
Latch: When the input value is over or under the High/Low limit, the 
alarm signal will be latched till clicking the “Clear Latch” button. 
Note:  The alarm types of ADAM-5080 include “Disable” and “Latch 
only. 