User manual
Chapter 3 
Hardware Installation Guide 
3-4    Wiring and Connections This section provides basic 
information on wiring the power supply, I/O units, and network 
connection. 
3-4-1 Power supply wiring 
Although the ADAM-5000/TCP Series systems are designed for a 
standard industrial unregulated 24 V DC power supply, they accept 
any  power unit that supplies within the range of +10 to +30 VDC. The 
power supply ripple must be limited to 200 mV peak-to-peak, and the 
immediate ripple voltage should be maintained between +10 and +30 
VDC. Screw termi- nals +Vs and GND are for power supply wiring. 
Note:  The wires used should be sized at least 2 mm. 
Power Supply 
+
+Vs 
+10~+30 V
DC
- 
GND 
COM 
DATA+ 
DATA- 
Figure 3-6: ADAM-5000/TCP power wiring 
3-6  ADAM-5000/TCP User’s Manual 