User manual
Appendix B  Data Formats and I/O Ranges 
Module 
Range 
Code 
Input Range 
Description 
Data Formats 
Maximum 
Specified 
Signal 
Minimum 
Specified 
Signal 
Displayed 
Resolution 
Actual 
Value 
Engineering 
Units 
+760.00  +000.00  0.1°C 
% of FSR  +100.00  +000.00  0.01% 
0Eh 
Type J 
Thermocouple 
0°C to 760°C   
Two's 
Complement 
7FFF  0000  1 LSB 
Reading/ 
10 
Engineering 
Units 
+1370.0  +0000.0  0.1°C 
% of FSR  +100.00  +000.00  0.01% 
0Fh 
Type K 
Thermocouple 
0°C to 1370°C 
Two's 
Complement 
7FFF  0000  1 LSB 
Reading/ 
10 
Engineering 
Units 
+400.00  -100.00  0.1°C 
% of FSR  +100.00  -025.00  0.01% 
10h 
Type T 
Thermocouple 
-100°C to 
400°C 
Two's 
Complement 
7FFF  E000  1 LSB 
Reading/ 
10 
Engineering 
Units 
+1000.00  +0000.0  0.1°C 
% of FSR  +100.00  ±000.00  0.01% 
11h 
Type E 
Thermocouple 
0°C to 1000°C 
Two's 
Complement 
7FFF  0000  1 LSB 
Reading/ 
10 
Engineering 
Units 
+1750.0  +0500.0  0.1°C 
% of FSR  +100.00  +028.57  0.01% 
12h 
Type R 
Thermocouple 
500°C to 
1750°C 
Two's 
Complement 
7FFF  2492  1 LSB 
Reading/ 
10 
Engineering 
Units 
+1750.0  +0500.00  0.1°C 
% of FSR  +100.00  +028.57  0.01% 
13h 
Type S 
Thermocouple 
500°C to 
1750°C 
Two's 
Complement 
7FFF  2492  1 LSB 
Reading/ 
10 
Engineering 
Units 
+1800.0  +0500.0  0.1°C 
% of FSR  +100.00  +027.77  0.01% 
ADAM-5018 
14h 
Type B 
Thermocouple 
500°C to 
1800°C 
Two's 
Complement 
7FFF  2381  1 LSB 
Reading/ 
10 
B-6 ADAM-5000/TCP User’s Manual 