User manual
Appendix B 
Data Formats and I/O Ranges 
B.2    Analog Input Ranges - ADAM-5017 
Module 
Range 
Code 
Input 
Range 
Description 
Data 
Formats 
+F.S. Zero -F.S. 
Displayed 
Resolution
Actual 
Value 
Engineering 
Units 
+10.000 ±00.000
-
10.000
1 mV 
% of FSR  +100.00 ±000.00
-
100.00
0.01% 
08h ±10 V 
Two's 
Complement
7FFF 0000 8000 1 LSB 
Reading/ 
1000 
Engineering 
Units 
+5.0000 ±0.0000
-
5.0000
100.00 µV
% of FSR  +100.00 ±000.00
-
100.00
0.01% 
09h ±5 V 
Two's 
Complement
7FFF 0000 8000 1 LSB 
Reading/ 
1000 
Engineering 
Units 
+1.0000 ±0.0000
-
1.0000
100.00 µV
% of FSR  +100.00 ±000.00
-
100.00
0.01% 
0Ah ±1 V 
Two's 
Complement
7FFF 0000 8000 1 LSB 
Reading/ 
10000 
Engineering 
Units 
+500.00 ±000.00
-
500.00
10 µV 
% of FSR  +100.00 ±000.00
-
100.00
0.01% 
0Bh ±500 mV 
Two's 
Complement
7FFF 0000 8000 1 LSB 
Reading/ 
10 
Engineering 
Units 
+150.00 ±000.00
-
150.00
10 µV 
% of FSR  +100.00 ±000.00
-
100.00
0.01% 
0Ch ±150 mV 
Two's 
Complement
7FFF 0000 8000 1 LSB 
Reading/ 
100 
Engineering 
Units 
+20.000 ±00.000
-
20.000
1 µV 
% of FSR  +100.00 ±000.00
-
100.00
0.01% 
ADAM-
5017 
0Dh ±20 mA 
Two's 
Complement
7FFF 0000 8000 1 LSB 
Reading/ 
1000 
4  
ADAM-
5000/TCP 
User’s 