User manual
Planning Your Application Program 
$aaSiCjRhC 
Name  Read Alarm Connection 
Chapter 6 
Description  Return the High/Low alarm limit output connection 
of a specified input channel in the addressed ADAM- 
5000/TCP system 
Syntax $aaSiCjRhC(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of an ADAM-5000/ 
TCP system. SiCj identifies the desired slot i and the 
desired chan- nel j. RhC is the command for reading 
Alarm Connection. h indicates alarm type and can 
have the  value H  = High alarm, L = Low alarm 
(cr) represents terminating character, carriage return 
(0Dh) 
Response !aaSkCn(cr) if the command was valid There is no 
response if the system detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
aa represents the 2-character hexadecimal Modbus 
network address of the corresponding ADAM-5000/ 
TCP system. 
SkCn  identifies the desired slot k and the desired 
digital output point n (n : 0 to F) to which the input 
alarm is connected. If the values of k and n are ‘*’, 
the analog input has no connection with a digital 
output point. 
ADAM-5000/TCP User’s Manual 
6-179 