User manual
Planning Your Application Program 
$aaSiCjAh 
Name  Read Alarm Disable/Latch 
Chapter 6 
Description  Return the alarm mode for the specified channel. 
Syntax $aaSiCjAh(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of an ADAM-5000/ 
TCP system. SiCj identifies the desired slot i and the 
desired chan- nel j. 
A is the Read Alarm Mode command. 
h indicates alarm type and can have the value H = 
High alarm, L = Low alarm 
(cr) represents terminating character, carriage return 
(0Dh) 
Response !aap(cr) if the command was valid There is no 
response if the system detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
aa represents the 2-character hexadecimal Modbus 
address of the corresponding ADAM-5000/TCP sys- 
tem. 
p indicates alarm mode. 
p=D, if alarm is Disable. 
P=L, if alarm is Latch. 
(cr) represents terminating character, carriage return 
(0Dh) 
ADAM-5000/TCP User’s Manual 
6-173 