User manual
Planning Your Application Program 
$aaSiCjAhEs 
Name  Set Alarm Disable/Latch 
Chapter 6 
Description  The addressed counter module is instructed to set 
alarm disable or latch. 
Syntax $aaSiCjAhEs(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of an ADAM-5000/ 
TCP system. SiCj identifies the desired slot i and the 
desired chan- nel j. AhEs is the command for setting 
Alarm Disable/Latch Mode command. 
h indicates alarm type and can have the value H = 
High alarm, L = Low alarm 
s indicates alarm enable/disable and can have the 
value D = Disable, E=Enable 
(cr) represents terminating character, carriage return 
(0Dh) 
Response !aa(cr) if the command was valid There is no 
response if the system detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
aa represents the 2-character hexadecimal Modbus 
network address of the corresponding ADAM-5000/ 
TCP system. 
(cr) represents terminating character, carriage return 
(0Dh) 
ADAM-5000/TCP User’s Manual 
6-171 