Planning Your Application Program 
Chapter 6 
@aaSiCjP(data) 
Name  Set Initial Counter Value 
Description  Set initial counter value for counter of the specified 
counter module. 
Syntax @aaSiCjP(data)(cr) 
@ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal address of the ADAM-5000/TCP system. 
SiCj identifies the I/O slot i and the channel j for the 
module you want to return a prior value. P represents 
Set Initial Counter Value command. 
(data) is initial value from 0 to 4294967296. Be aware 
that (data) has 10 characters. 
(cr) is the terminating character, carriage return (0Dh) 
Response !aa(cr) if the command is valid. 
?aa(cr) if an invalid operation was entered. There is 
no response if the module detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
? delimiter character indicating the command was in- 
valid. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal address of an ADAM-5000/TCP system. 
(cr) is the terminating character, carriage return (0Dh) 
Example  command: @01S3C2P0000004369(cr) 
response: !01(cr) 
The channel 2 of ADAM-5080 in slot 3 in ADAM- 
5000/TCP system at address 01h is instructed to set 
initial counter value. The initial counter value is 4369. 
ADAM-5000/TCP User’s Manual 