User manual
Planning Your Application Program 
$aaSiCj5s 
Name  Set Counter Start/Stop 
Chapter 6 
Description  Request the addressed counter/frequency 
module to start or stop the counting. 
Syntax $aaSiCj5s(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of the ADAM-5000/ 
TCP system. 
SiCj identifies the I/O slot i and the channel j of the 
module you want to set. 
5 is the command for setting counter Start/Stop. 
s represents start/stop command. s=0 indicate 
stop counter. s=1 indicate start counter. 
(cr) is the terminating character, carriage return (0Dh) 
Response !aa(cr) if the command is valid. 
?aa(cr) if an invalid operation was entered. There is 
no response if the module detects a syntax error or 
communication error or if the specified ad- dress 
does not exists. 
! delimiter character indicating a valid command was 
received. 
? delimiter character indicating the command was 
invalid. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of an ADAM-5000/ 
TCP system. 
(cr) is the terminating character, carriage return (0Dh) 
ADAM-5000/TCP User’s Manual 
6-161 