User manual
Planning Your Application Program 
$aaSiCjAhU(data) 
Name  Set Alarm Limit 
Chapter 6 
Description  Set the High/Low alarm limit value for the specified 
input channel of a specified ADAM-5000/TCP sys- 
tem. 
Syntax $aaSiCjAhU(data)(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of an ADAM-5000/ 
TCP system. SiCj identifies the desired slot i and the 
desired chan- nel j. 
AhU is the Set Alarm Limit command. 
h indicates alarm type and can have the value H = 
High alarm, L = Low alarm 
(data) represents the desired alarm limit setting. The 
value is from 0 to 4294967295. Be aware that (data) 
has 10 characters. 
(cr) represents terminating character, carriage return 
(0Dh) 
Response !aa(cr) if the command was valid There is no 
response if the system detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
aa represents the 2-character hexadecimal Modbus 
network address of the corresponding ADAM-5000/ 
TCP system. 
ADAM-5000/TCP User’s Manual 
6-181 