$aaSiCj6 
Name  Clear Counter 
Chapter 6 
Description  Clear the counters of the specified counter/frequency 
module 
Syntax $aaSiCj6(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of the ADAM-5000/ 
TCP system. SiCj identifies the I/O slot i and the 
channel j for the module you want to return a prior 
value. 
6 is the command for clearing counter. 
(cr) is the terminating character, carriage return (0Dh) 
Response !aa(cr) if the command is valid. 
?aa(cr) if an invalid operation was entered. There is 
no response if the module detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
? delimiter character indicating the command was in- 
valid. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of an ADAM-5000/ 
TCP system. 
(cr) is the terminating character, carriage return (0Dh) 