User manual
Chapter 6 
Planning Your Application Program 
$aaSi0 
Name  Read Digital filter scale 
Description  Read the filter seconds to start to measure the input 
signal. 
Syntax $aaSi0(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal address of the ADAM-5000/TCP system which 
is to be calibrate. 
Si identifies the I/O slot which is to be accessed. 
0 is the command for reading digital filter scale. 
(cr) is the terminating character, carriage return (0Dh) 
Response !aa(data)(cr) if the command is valid. 
?aa(cr) if an invalid operation was entered. There is 
no response if the module detects a syntax error or 
communication error or if the specified ad- dress 
does not exists. 
! delimiter character indicating a valid command was 
received. 
? delimiter character indicating the command was in- 
valid. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal address of an ADAM-5000/TCP system. 
(data) represents filter seconds from 8 
µs~65000
µs. 
Be aware that (data) has 5 characters. 
(cr) is the terminating character, carriage return (0Dh) 
Example  command: $01S30(cr) 
response: !0100765(cr) The command requests the 
ADAM-5080 in slot 3 of the ADAM-5000/TCP 
system at address 01h to read the filter seconds. The 
module responds with 765m seconds. 
6-160 ADAM-5000/TCP User’s Manual 