User manual
Chapter 6 
Planning Your Application Program 
#aaSi 
Name  Read All Channel Counter (Frequency) Data 
Description  Return the input value of all channels for the speci- 
fied input module for a specified system in engineer- 
ing unit only. 
Syntax #aaSi(cr) 
# is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of the ADAM-5000/ 
TCP system you want to interrogate. Si is the I/O 
slot of ADAM-5000 system you want to read. 
(cr) is the terminating character, carriage return (0Dh) 
Response  >(data) (data) (data) (data) (cr) if the command is valid. 
?aa (cr) if an invalid operation was entered. There 
is no response if the module detects a syntax error 
or communication error or if the specified ad- dress 
does not exists. 
> is a delimiter character. 
? is a delimiter character indicating the command 
being invalid. 
(data) is the input value in engineering units of the 
interrogated module of the specified system. If the 
numbers of (data) are ten ,counter/frequency mode 
is in decimal format. If the numbers of (data) are eight, 
counter/frequency mode is in hexadecimal format. If 
(data) = “ “, it means the channel is invalid. 
(cr) is the terminating character, carriage return (0Dh). 
6-154 ADAM-5000/TCP User’s Manual 