User manual
Chapter 6 
Planning Your Application Program 
$aaSiCj1 
Name  20 mA Calibration 
Description  Directs the specified channel to store parameters fol- 
lowing a calibration for 20 mA output 
Syntax $aaSiCj1(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal address of the ADAM-5000/TCP system. SiCj 
identifies the I/O slot i (i : 0 to 7) and the channel j (j : 
0 to 3) of the module you want to calibrate. 
1 is the 20 mA calibration command. 
(cr) is the terminating character, carriage return (0Dh) 
Response !aa(cr) if the command is valid. 
?aa(cr) if an invalid operation was entered. There is 
no response if the module detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
? delimiter character indicating the command was in- 
valid. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal address of an ADAM-5000/TCP system. 
(cr) is the terminating character, carriage return (0Dh) 
Note:  Before issuing the 20 mA Calibration command, the analog out- 
put module should be trimmed to the correct value using the 
Trim Calibration command. Either a mA meter or a resistor and 
voltmeter should be connected to the module’s output. 
6-136 ADAM-5000/TCP User’s Manual 