Example  command: $01S0C1AHU+080.00(cr) 
response: !01(cr) 
Channel 1 of slot 0 in the ADAM-5000/TCP system 
at address 01h is configured to accept type-T ther- 
mocouple input. The command will set its High alarm 
limit to +80°C. 
The system confirms the command has 
been re- ceived. 
Note:  An analog input module requires a maximum of 2 seconds after 
it receives a Set Alarm Limit command to let the settings take 
effect. During this interval, the module cannot be addressed to 
perform any other actions. 