User manual
Chapter 6 
Planning Your Application Program 
(cr) represents terminating character, carriage return 
(0Dh) 
Example  command: $01S0C1RLC(cr) 
response: !01S1C0(cr) Channel 1 of slot 0 in the 
ADAM-5000/TCP system at address 01h is 
instructed to read its Low alarm output   
connection. 
The  system  responds  that  the  Low  alarm  
output connects to the digital output at point 0 of 
slot 1 in the same ADAM-5000/TCP system. 
6-120 ADAM-5000/TCP User’s Manual 