Analog Input Alarm Command Set 
Command 
Syntax 
Command 
Name 
Description 
$aaSiCjAhs  Set Alarm Mode Sets the High/Low alarm in either 
Momentary or Latching mode 
$aaSiCjAh  Read Alarm 
Mode 
$aaSiCjAhEs  Enable/Disable 
Alarm 
$aaSiCjCh  Clear Latch 
Alarm 
Returns the alarm mode for the 
specified channel. 
Enables or Disables the High/Low 
alarm of the specified channel 
Resets a latched alarm 
$aaSiCjAhCSk- 
Cn 
Set Alarm 
Connection 
Connects the High/Low alarm of a 
specified input channel to a 
specified digital output channel 
$aaSiCjRhC  Read Alarm 
Connection 
Returns the alarm limit output 
connection of a specified input 
channel 
$aaSiCjAhU(da- 
ta) 
Set Alarm Limit  Sets the High/Low alarm limit 
value for the specified input 
channel 
$aaSiCjRhU  Read Alarm 
Limit 
$aaSiCjS  Read Alarm 
Status 
Returns the High/Low alarm limit 
value for the specified input 
channel 
Reads whether an alarm occurred 
for a specified input channel 
Table 6-8 Analog Input alarm command set table 