User manual
Chapter 6 
Planning Your Application Program 
$aaSiCjRhU 
Name  Read Alarm Limit 
Description  Returns the High/Low alarm limit value for the speci- 
fied input channel in the addressed ADAM-5000/ 
TCP system 
Syntax $aaSiCjRhU(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of an ADAM-5000/ 
TCP system. 
SiCj identifies the desired slot i (i : 0 to 7) and the 
desired analog input channel j (j : 0 to 7). RhU is the 
Read Alarm Limit command. 
h indicates alarm type and can have the value H = 
High alarm, L = Low alarm 
(cr) represents terminating character, carriage return 
(0Dh) 
Response !aa(data)(cr) if the command was valid There is no 
response if the system detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
aa represents the 2-character hexadecimal Modbus 
network address of the corresponding ADAM-5000/ 
TCP system. 
(data) represents the desired alarm limit setting. The 
format is always in engineering units. 
(cr) represents terminating character, carriage return 
(0Dh) 
6-104 ADAM-5000/TCP User’s Manual 