User manual
Chapter 6 
Planning Your Application Program 
$aaSiCjAhU(data) 
Name  Set Alarm Limit 
Description  Sets the High/Low alarm limit value for the specified 
input channel of a specified ADAM-5000/TCP sys- 
tem. 
Syntax $aaSiCjAhU(data)(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of an ADAM-5000/ 
TCP system. 
SiCj identifies the desired slot i (i : 0 to 7) and the 
desired analog input channel j (j : 0 to 7). AhU is the 
Set Alarm Limit command. 
h indicates alarm type and can have the value H = 
High alarm, L = Low alarm 
(data) represents the desired alarm limit setting. The 
format is always in engineering units. 
(cr) represents terminating character, carriage return 
(0Dh) 
Response !aa(cr) if the command was valid There is no 
response if the system detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
aa represents the 2-character hexadecimal Modbus 
network address of the corresponding ADAM-5000/ 
TCP system. 
(cr) represents terminating character, carriage return 
(0Dh) 
6-102 ADAM-5000/TCP User’s Manual 