User manual
Understanding Your System 
Chapter 1 
1-2  Major Features 
1-2-1 Communication Network 
By adopting a 32-bit RISC CPU, the ADAM-5000/TCP Series has 
greatly ad- vanced data processing abilities for the user, especially for 
network com- munications (response time < 5ms). There is a standard 
RJ-45 modular jack Ethernet port on the ADAM-5000/TCP’S CPU 
board, and I/O mod- ules field signals would be able to link with the 
Ethernet directly without assistance from other hardware devices such as 
converters or data gate- ways. The communication speeds can be auto-
switched between 10 M and 100 Mbps data transfer rate depending 
upon the network environ- ment. Through an Ethernet network, your 
DA&C systems, computer workstations, and higher-level enterprise 
MIS servers can access plant- floor data. Such data can be used in 
system supervising, product sched- uling, statistical quality control, and 
more. 
1-2-2 Modbus/TCP Protocol Modbus/TCP is one of the most 
popular standards for industrial Ethernet networks. Following this 
communication protocol, the ADAM-5000/TCP Series is easy to integrate 
with any HMI software packages or user-developed applications that 
support Modbus. Users do not have to prepare a specific driver for the 
ADAM-5000/TCP Series when they install the DA&C sys- tem with 
their own operating application. It will certainly reduce engineer effort. 
Moreover, the ADAM-5000/TCP Series works as a Modbus data server. 
It allows eight PCs or tasks to access its current data simultaneously 
from anywhere: LAN, Intranet, or Internet. 
1-2-3   Hardware Capacity & Diagnostic Advantech’s 
ADAM-5000/TCP Series is designed with a high I/O capacity and 
supports all types of ADAM-5000 I/O modules. Providing eight slots for 
any mixed modules, this DA&C system handles up to 128 I/O points 
(four ADAM-5024s allowed). Different from other main units, the ADAM- 
5000/TCP Series not only has a higher I/O capacity, but it also has a 
smarter diagnostic ability. There are eight indicators on the front case of 
the CPU module. Users can read the system status clearly, including 
power, CPU, Ethernet link, Communication active, communication rate, 
and more. In addition, there are also Tx and Rx LEDs on the Ethernet 
port, indicating data transfer and reception. 
ADAM-5000/TCP User’s Manual 
1-3 