User manual
Planning Your Application Program 
#aaSiCj 
Name  Specified Analog Data In 
Chapter 6 
Description  Returns the input value of a specified channel of a 
specified analog input module in a specified ADAM- 
5000/TCP system in engineering units or 
two’s complement data format 
Syntax #aaSiCj(cr) 
# is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of the ADAM-5000/ 
TCP system you want to configure. 
Si identifies the I/O slot (i:0 to 7) of ADAM-5000/ 
TCP system you want to read. 
Cj identifies the channel you want to read. 
(cr) is the terminating character, carriage return (0Dh). 
Response !(data)(cr) if the command is valid. (Engineering Unit 
Data Format) 
!(dddd)(cr) if the command is valid. (Two’s Comple- 
ment Data Format) if an invalid operation was 
entered. There is no response if the module detects 
a syntax error or communication error or if the 
specified ad- dress does not exist. 
! delimiter character indicating a valid command was 
received. 
? delimiter character indicating the command was 
invalid. 
ADAM-5000/TCP User’s Manual 
6-87 