Name  Initialize EEPROM data 
Chapter 6 
Description  Initializes all EEPROM data in a specified analog in- 
put module to their default values. This command is 
sent following a failed attempt to calibrate a module 
(the module shows no effect from an attempted cali- 
bration). Following initialization, the problem mod- 
ule should readily accept calibration. 
Syntax $aaSiER(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of the ADAM-5000/ 
TCP system. Si identifies the I/O slot for which you 
wish to initial- ize all EEPROM data. ER is Initialize 
all EEPROM data command. 
(cr) is the terminating character, carriage return (0Dh) 
Response !aa(cr) if the command is valid. 
?aa(cr) if an invalid operation was entered. There is 
no response if the module detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
? delimiter character indicating the command was 
invalid. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus address of an ADAM-5000/TCP sys- 
tem. 
(cr) is the terminating character, carriage return (0Dh 