User manual
Chapter 6 
Planning Your Application Program 
$aaSi1 
Name  RTD Zero Calibration 
Description  Calibrates a specified RTD input module of a speci- 
fied system to correct for offset errors. 
Syntax $aaSi1(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal address of the ADAM-5000/TCP system which 
contains the module which is to be calibrated. 
Si identifies the slot i (i:0 to 7) containing the RTD 
module to be calibrated. 
1 represents the zero calibration command. 
(cr) is the terminating character, carriage return (0Dh). 
Response !aa(cr) if the command is valid. 
?aa(cr) if an invalid operation was entered. There is 
no response if the module detects a syntax error or 
communication error or if the specified ad- dress 
does not exist. 
! delimiter character indicating a valid command was 
received. 
? delimiter character indicating the command was in- 
valid. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal address of an ADAM-5000/TCP system. 
(cr) is the terminating character, carriage return (0Dh). 
6-60 ADAM-5000/TCP User’s Manual 