User manual
Chapter 6 
Planning Your Application Program 
$aaSiER 
Name  Initialize EEPROM Data 
Description  Initializes all EEPROM data in a specified analog in- 
put module to their default values. This command is 
sent following a failed attempt to calibrate a module 
(the module shows no effect from an attempted cali- 
bration). Following initialization, the problem 
module should readily accept calibration. 
Syntax $aaSiER(cr) 
$ is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of the ADAM-5000/ 
TCP system. Si identifies the I/O slot in which you 
wish to initial- ize all EEPROM data. ER represents 
the initialize EEPROM data command. 
(cr) is the terminating character, carriage return (0Dh) 
Response !aa(cr) if the command is valid. 
?aa(cr) if an invalid operation was entered. 
There is no response if the module detects a syntax 
error or communication error or if the specified ad- 
dress does not exist. 
! delimiter character indicating a valid command was 
received. 
? delimiter character indicating the command was 
invalid. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of an ADAM-5000/ 
TCP system. 
(cr) is the terminating character, carriage return (0Dh) 
6-56 ADAM-5000/TCP User’s Manual 