Planning Your Application Program mal Modbus 
network address of an ADAM-5000/ TCP system. 
(cr) is the terminating character, carriage return (0Dh). 
Example  command: %01000A40(cr) 
response: !01(cr) 
The ADAM-5000/TCP system with address 01h is 
configured to a baud rate of 115.2 Kbps and with 
checksum generation or validation. 
The response indicates that the command was re- 
ceived. Wait 7 seconds to let the new configuration 
setting take effect before issuing a new command to 
the system. 
Note:  All configuration parameters can be changed dynami- 
cally, except checksum and baud rate parameters. 
They can only be altered when the INIT* terminal is 
grounded. 
Baud Rate Code  Baud Rate 
03h  1200 bps 
04h  2400 bps 
05h  4800 bps 
06h  9600 bps 
07h  19.2 Kbps 
08h  38.4 Kbps 
09h  57.6 Kbps 
0Ah  115.2 Kbps 
Table 6-3 Baud rate codes 