User manual
Planning Your Application Program 
%aannccff 
Name  Configuration 
Chapter 6 
Description  Sets RS-485 network baud rate and checksum status 
for a specified ADAM-5000/TCP system 
Syntax %aannccff(cr) 
% is a delimiter character. 
aa (range 00-FF) represents the 2-character hexadeci- 
mal Modbus network address of the ADAM-5000/ 
TCP system you want to configure. 
nn is reserved for system use. Its default value is 
00h. 
cc represents the baud rate code. 
ff is a hexadecimal number that equals the 8-bit pa- 
rameter representing checksum status. The sixth bit 
represents  the  checksum  status;  1  means 
enabled while 0 means disabled. The other bits are 
not used and are set to 0. 
(cr) is the terminating character, carriage return (0Dh). 
Response !aa (cr) if the command is valid. 
?aa (cr) if an invalid parameter was entered or if the 
INIT* terminal was not grounded when attempting 
to change baud rate or checksum settings. There is 
no response if the module detects a syntax 
error, communication error or if the specified 
address does not exist. 
! delimiter character indicating a valid command was 
received. 
? delimiter character indicating the command was in- 
valid. 
aa (range 00-FF) represents the 2-character hexadeci- 
ADAM-5000/TCP User’s Manual 
6-41 