Datasheet
Programmable Automation Controllers
Features
Introduction
The ADAM-5000L/TCP and ADAM-5000/TPC are both Ethernet-based I/O systems. Without a repeater, the ADAM-5000L/TCP and ADAM-5000/TCP can cover a communication 
distance up to 100 m. This allows remote configuration via Ethernet and eight PCs can simultaneously access the data. The ADAM-5000L/TCP and ADAM-5000/TCP are the solutions 
for easy configuration and efficient management. It is an ideal and cost-effective solution for eAutomation architecture.
ADAM-5000L/TCP 
ADAM-5000/TCP
  ARM 32-bit RISC CPU
  10/100Base-T auto-negotiation high-speed communication port
  Supports Modbus/TCP for easy integration
  Supports UDP event handling function
  Up to 100 m communication distance w/o repeater
  Allows remote configuration via Ethernet
  Allows concurrent access for 8 host PCs
  4 I/O slots for up to 64 points and 8 I/O slots for up to 128 points data 
monitoring and control
  1500 V
DC
 isolation for Ethernet communication
  Built-in watchdog timer for system auto-reset
  Windows utility 
- I/O modules configuration and calibration 
- Network auto searching 
- Data stream setting 
- Current status monitoring and alarm trigger
  Provides C and .NET class library to develop applications
  Support GCL function for easy IO interlocking logic
Specifications
Control System
  CPU  32-bit ARM RISC
  I/O Slots  ADAM-5000L/TCP: 4 
ADAM-5000/TCP: 8
  Memory  Flash ROM: 512 KB 
RAM: 4 MB
  Operating System  Real-time OS
  LED Indicators  Power (3.3 V, 5 V) 
CPU 
Communication (Link, Active, 10/100 Mbps, Tx, Rx) 
Battery
Communications (Ethernet)
  Data Transfer Rate  Up to 100 Mbps
  Event Response Time  < 5 ms
  Interface  1 x 10/100Base-T (RJ-45)
  Wiring  UTP, category 5 or greater
Communications (Serial)
  Comm. Distance  RS-485: 1.2 km (4000 feet) 
RS-232: 15 m
  Comm. Protocol  Modbus/RTU
  Data Transfer Rate  Up to 115.2 kbps
  Interface  1 x DB9-M for RS-485 
1 x DB9-F for RS-485 
1 x DB9-F for RS-232
  Max. Nodes  12 (in RS-485 daisy-chain network for Remote I/O 
connection)
Power
  Power Consumption  4.0 W @ 24 V
DC
 (ADAM-5000L/TCP) 
(not including I/O modules) 
5.0 W @ 24 V
DC
 (ADAM-5000/TCP) 
(not including I/O modules)
  Power Input  Unregulated 10 ~ 30 V
DC
Software
  C and .NET Class Library
  Windows Utility  Network setting, I/O configuration & calibration, data 
stream, alarm setting
  Modbus/TCP OPC Server
Protection
  Communication Line  3.000 V
DC 
Isolation
  I/O Module Isolation  3.000 V
DC
  LAN Communication  1.500 V
DC
  Overvoltage Protection  Yes
  Power Reversal  Yes 
Protection
General
  Certification  CE, FCC class A
  Connectors  1 x DB9-M/DB9-F/screw terminal for RS-485 
(communication) 
1 x DB9-F for RS-232 (internal use) 
1 x Screw-terminal for power input 
1 x RJ-45 for LAN
  Dimensions (W x H x D) ADAM-5000L/TCP: 231 x 110 x 75 mm 
ADAM-5000/TCP:  355 x 110 x 75 mm
  Enclosure  ABS+PC
  Mounting  DIN-rail, wall
Environment
  Operating Humidity  5 ~ 95%, non-condensing
  Operating Temperature  - 10 ~ 70°C (14 ~ 158°F)
  Storage Temperature  - 25 ~ 85°C (-13 ~ 185°F)
Ordering Information
  ADAM-5000L/TCP  4-slot Ethernet-based Distributed DA & C System
  ADAM-5000/TCP  8-slot Ethernet-based Distributed DA & C System
4-slot Distributed DA&C System 
for Ethernet
8-slot Distributed DA&C System 
for Ethernet
ADAM-5000/TCP  ADAM-5000L/TCP
RoHS
COMPLIANT