User Manual

32 ADAM-4572 User's Manual
Surge protection for RS-485 line and power supply
The ADAM-4572 provides surge protection for the power input and
some vital part of the internal circuitry. For the power input, the surge
protection is up to 34V, and when the instantaneous power output rises
up to 200 Watts, the circuit will break to protect the device from being
damaged. For RS-485/422, the surge protection is up to 18V, and when
the instantaneous power output rises up to 200 Watts, the circuit will
break to protect the device from damages.
4.2 Hardware Specifications
Protocol: TCP, UDP, IP, ARP
Modbus: Modbus/RTU, Modbus/ASCII, Modbus/TCP
Network Port: 10 BASE-T IEEE 802.3, 100 BASE-TX IEEE 802.3u
RJ-45 connector
Serial Port: RS-232/485/422
IO plug-in connector (20-pin terminal)
Transmission speed: 300 bps to 115.2 kbps
Format: parity: odd, even, none
Data bit: 7, 8
Stop bit: 1, 2
Compatibility: Ethernet: version 2.0/IEEE 802.3, IEEE 802.3u
Modbus/Serial: Modbus/ASCII, Modbus/RTU
Network: Modbus/TCP
Diagnostic LEDs: Network: Tx/Rx, Link, Speed (10/100Mbps), Power
Serial: Tx/Rx, Status
Utility Software: Windows-based, device auto-searching
Device Setting: name, description, serial port
Compatible with application software running on Modbus/TCP
standard
Power Requirements: unregulated 10 to 30 V
DC
with protection from
power surge