INIT* state defaults:
Baud rate: 9600
Address: 00h
Checksum: disabled
Forcing th e mo dule in INIT* state does not ch ange an y p arameters in th e
module’s EE PROM. When the module is in the INIT* state wi th its INIT*
and GND termin als sh orted, all co nfiguration setting s can be ch anged, and
the module will respond to all other commands normally.
Notice:
Init Mode
When the switch is set to the initial mode, the module will operate
with its factory settings. (Address 0 with data format 9600, N, 8, 1).
Normal Mode
When the switch is set to the normal mode, the module will operate
with user-defined settings. A power reset will not alter these settings.
5. Connect computer to the ADAM I/O module using a RS-232 to RS-485,
or USB to RS-485 converter.