User Manual
Appendix A
Appendix A Technical Specification A
-3
Table A-2 ADAM-4011 Range Accuracy for Thermocouple
Input
Range
Code
(Hex)
Input Range
Typical
Accuracy
Maximum
Error
Units
0E
J thermocouple
0 to760 ℃
±0.5 ±0.75
℃
0F
K thermocouple
0 to 1370 ℃
±0.5 ±0.75
℃
10
T thermocouple
-100 to 400 ℃
±0.5 ±0.75
℃
11
E thermocouple
0 to 1000 ℃
±0.5 ±0.75
℃
12
R thermocouple
500 to 1750 ℃
±0.6 ±1.5
℃
13
S thermocouple
500 to 1750 ℃
±0.6 ±1.5
℃
14
B thermocouple
500 to 1800 ℃
±1.2 ±2.0
℃