16
ADAM 4000 Series User’s Manual
4. Execute th e Sp an Calib ration co mmand. This can b e done throug h
the ADAM u tility software. (Please see "A/O 10 V C alibration"
option in the Calibration sub-menu of the ADAM utility software.)
Figure 8-9 Span Calibration
5. Check the actual output value at the terminals. If this does not equal
0 V or 10 V, u se th e Trim Calib ration co mmand to ch ange th e
output v alue. Th is is don e throug h th e ADAM utility software.
(Use th e arrow key to adj ust th e ou tput value after execu ting th e
"A/O 0V Calib ration" or "A/O 10 V Calibratio n". Righ t and Up
keys mean increasing, and Left and Down keys mean decreasing).