Calibration
8-
14
ADAM 4000 Series User’s Manual
4. Issue the Analog Data Out command to the module with an output
value of 4 mA.
5. Check the actual output value at the terminals. If it does not equal
to 4 m A, use th e “Trim ” op tion in th e “Calib rate” su b m enu to
change th e actu al ou tput. Trim th e module un til th e millimeter
indicates e xactly 4 m A. In t he ca se of using a voltage meter with
shunt resistor, the voltage meter should indicate exactly 1 V. (When
calibrating fo r 20 m A u sing vo ltage m eter and shu nt resistor, t he
correct voltage would be 5 V.)
6. Issue th e 4 mA Calibratio n command to indicate that the ou tput is
calibrated. The calib rated parameters sho uld be stored i n th e
modules EEPROM.
7. Execute an Analog Data Out command with an output value of 20
mA, and the output will approximately be 20 mA.
8. Continue executing the Trim Calib ration command until the output
current is equal to exactly 20 mA.
9. Execute the 20 mA Calibration command until th e present output is
exactly 20 m A. The analog output m odule will store its c alibrated
parameters in EEPROM.