User Manual
Calibration
8-
2
ADAM 4000 Series User’s Manual
Analog i nput/output m odules are calibrate d whe n you receive them .
However, cal ibration is so metimes requ ired. No screwdriver is
necessary because calib ration is don e in so ftware. Calib ration
parameters are stored in the ADAM module’s onboard EEPROM.
The ADAM modules com e with u tility soft ware that supports the
calibration of anal og i nput and a nalog out put. Aside f rom t he
calibration that is carried out through software, the modules incorporate
automatic Zero Calibration and automatic Span Calib ration at boot-up
or reset.
8.1 Analog Input Module Calibration
Models: ADAM-4011, 4011D, 4012, 4016, 4017, 4017+, 4018, 4018+,
4018M, 4019+
1. Set modules as initial mode before applying
power t o t he m odule
and let it warm up for about 30 minutes
2. Assure t hat t he m odule i s co rrectly i nstalled an d i s p roperly
configured for th e inp ut range th at you wan t to calibrate. You can
do t his b y u sing th e ADAM u tility so ftware. (Please refer t o
Appendix D, Utility Software.)
3. Use a p recise voltage s ource t o cal ibrate t he m odule t hrough + IN
and -IN terminals for ADAM-4011, 4011D and 4012. However, for
ADAM-4016, the calibrating voltage should be applied to terminals
Vin+ and Vin- (or Iin+ and Iin-). At last, Vin0+ and Vin0- are used
for calibration in ADAM-4017, 4017+, 4018, 4018+, 4018M, 4019
and 4019+ models.
Figure 8-1 Applying Calibration Voltage