User Manual

Digital I/O and Relay Output
Counter/Frequency Command Set
7-
28
ADAM 4000 Series User’s Manual
7.2 Counter/Frequency Module Command
7.2.1 Configuration, Counter Input and Display Command Set
Command
Syntax
Description
I/O Module
%AANNTTCCFF
Sets the address, input mode, baud rate, checksum
status and/or frequency gate time for a specified
counter/frequency module
4080,
4080D
$AA2
R
equests the return of the
c
onfiguration data from the
counter/frequency module
4080,
4080D
$AAF
R
equests the counter/frequency module to return the
version code of its firmware
4
080,
4080D
$AAM
R
equests the counter/frequency module
to return its
name
4080,
4080D
$AABS
Set the input signal mode of the specified
counter/frequency module to either non-isolated
(TTL) or photo-isolated.
4080,
4080D
$AAB
Read the input mode of the sp
ecified
counter/frequency module.
4080,
4080D
#AAN
Instructs the addressed counter/
frequency module to
read the counter or frequency value of counter 0 or
counter 1 and return the acquired data.
4080,
4080D
$AA8V
Select whether LED will display data fro
m the
counter/frequency module directly or from the host
computer.
4080D
$AA8
Read the LED Data Origin status which determines
whether LED will display data from the counter/
frequency module directly or from the host computer
4080D
$AA9(data)
The host c
omputer sends data to the addressed
module to display on its LED. This command is valid
only after selectting to display host computer data
($AA8V)
4080D