User Manual

Chapter 7
7-
19
ADAM 4000 Series User’s Manual
$AAM
Name Read Module Name command
Description The command requests the digital I/O module at address
AA to return its name
Syntax $AAM (cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address that you will access to.
M is the Read Module Name command.
(cr) is the terminating character, carriage return (ODh).
Response !AA(Module Name)(cr) if the command is valid.
There is no response if the module detects a syntax or
communication error, even or if the specified address does
not exist.
! is a delimiter character which indicates a valid command.
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
(Module Name) is the name of the module at address AA.
For example, 4052
(cr) is the terminating character, carriage return (ODh).
4050, 405
1
, 405
2
, 40
53
, 405
5
,
4056S, 4056SO, 4060, 4068, 4069