User Manual

5-64
ADAM 4000 Series User’s Manual
4016
$AAS
Name Start-up Voltage Output Configuration command
Description Stores t he pre sent analog output val ue o f the strain gauge
input module with address AA in the module’s non-volatile
register. The ou tput value will take effect upon start-up or
after a brownout.
Syntax $AAS(cr)
$ is a delimiter character.
AA (range 00-FF) represe nts the 2-cha racter hexadecimal
address of t he st rain ga uge i nput m odule wh ose a nalog
output is to be set.
S is the Start-up Voltage Output Configuration command.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(cr) if the command is valid.
?AA(cr) if an invalid command was issued.
There is no response if the module detects a syntax error or
communication e rror or if the s pecified a ddress does not
exist.
! delimiter character i ndicates a valid command wa s
received.
? delimiter character indicates the command was invalid.
AA (range 00-FF) represents the 2-character he xadecimal
address of the strain gauge input module.
(cr) is the terminating character, carriage return (0Dh).
NOTICE: A strain gauge input module requires a maximum of 6
milliseconds after it received a Startup Voltage Output
Configuration command to let the settings take effect. During
this interval, the module can not be addressed to perform any
other actions.