User Manual
Chapter 5
5-29
ADAM 4000 Series User’s Manual
4015, 4015T, 4017+, 4018+, 4019+
$AA8Ci
Name Read Single Channel Range Configuration command
Description This command read the input type and range configuration
of the specified channel in an analog input module.
Syntax $AA8Ci(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character he xadecimal
address of the analog input module which is to be read.
8 is the Read Si ngle C hannel Ran ge Co nfiguration
command.
Ci represents the specified input channel you want to read.
(cr) is the terminating character, carriage return (0Dh).
Response !AACiRrr(cr) if the command was valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication e rror or if the s pecified a ddress does not
exist.
! delimiter character i ndicates a valid command wa s
received.
? delimiter character indicates the command was invalid.
AA (range 00-FF) represents the 2-character he xadecimal
address of the analog input module.
Ci represents the specified input channel you read.
Rrr represents th e typ e and range settin g i n t he sp ecified
channel.
(Refer to Table 5-1 on Page 5-6 to check range codes)
(cr) represents terminating character, carriage return (0Dh).
Example command: $028C5(cr)
response: !02C5R21(cr)
The c ommand rea d the ra nge of c hannel 5 in the a nalog
input m odule at add ress 02. The response “R 21” m eans