User Manual

5-22
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013,
4015, 4015T, 4016
$AA4
Example com mand: $074(cr)
response: >071+5.8222(cr)
The command asks the analog input module at address 07h
to send its analog input data.
The a nalog i nput m odule responds wi th st atus = 1 , which
means that th is is th e first ti me that the data has been sen t
and that the data = +5.8222 Volts.
(Configured data format of the analog input module in this
case is engineering units.)
command:
$0 74(cr)
response: >0 70+5.8222(cr)
The command asks the analog input module at address 07h
to send its analog input data.
The a nalog i nput m odule responds wi th st atus = 0 , which
means that it has se nt t he s ame data at le ast once before,
and data = + 5.8222 V olts. Thi s c ould i ndicate t hat a
previous Sy nchronized Sa mpling command was n ot
received!
(Configured data format of the analog input module in this
case is engineering units.)