User Manual

5-20
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013,
4015, 4015T, 4016
#**
Name Sy nchronized Sampling command
Description Orders al l an alog i nput m odules t o sa mple t heir i nput
values and store the values in special registers.
Syntax #**
# is a delimiter character.
** is the Synchronized Sampling command.
The terminating character, in the form of a carriage return
(0Dh), is not required.
Response The a nalog i nput m odules will send no response after
executing the synchronized sampling command. In order to
retrieve th e data, a separate Read Sy nchronized Data
command has to be issued for every analog input module.
The pound sign (#) followed by two asterisks (**) does not
represent an optional value, bu t is t he actu al co mmand
string.